Project Summary Sheet

Project Objective:  LIMS Integration with SAP ERP System

Project Summary:

bullet

In-process testing is required at several stages in the steelmaking process in order to achieve the tight chemistry tolerances demanded of high quality steel; sampling probes are directly inserted into the liquid steel to retrieve samples which cool to form “lollipops”, or discs about the diameter of a quarter

bullet

A Level 2 VAX computer systems tracks the movement of steel “heats” (batches) from Basic Oxygen Furnace (BOF) vessels, through Ladle Metallurgical Facilities (LMF), Vacuum Carbon Degasser (VCD), and billet or bloom Casters; operators at each of these facilities use EASON keypad display terminals to identify each lollipop sample sent via a pneumatic tube system to a centralized chemlab

bullet

Arriving samples are announced to chemlab technicians by a voice synthesizer and are automatically identified on a PC Menu touch screen; a technician places the next lollipop sample into the sample preparation drawer and points to the corresponding sample ID on the Menu screen

bullet

The Applied Research Laboratories (ARL) Automated Metals Analyzer consists of a robotic sample preparation machine and an emissions spectrometer; the VAX downloads aim chemistries and min/max tolerances according to steel grade; when required, smaller samples are punched from the lollipop for high precision carbon and sulfur analyses on LECO devices and nitrogen analyzers

bullet

Heat chemistry results are automatically displayed back on the shop floor in just minutes; the VAX maintains sample identity throughout all phases of the analytical process through real-time communication with the 8 EASON sending stations, 4 PCs, 3 LECO machines, and 2 nitrogen analyzers; chemistry results are archived on the VAX and transmitted to the Level 3 ERP system for quality assurance use in downstream steel processing and shipping operations

Economic Summary:

bullet

Reduced costs through chemlab manpower reductions

bullet

Reduced analysis time through more consistent and automated sample preparation and the ability to prioritize in-process tests ahead of lower priority magazine tests

671 Columbia Rd., Suite 8, P.O. Box 450858, Westlake, OH 44145-0858  ·  (440) 899-1676  Fax (440) 899-9267